ASTM D93-06
Standard Test Methods for Flash Point by Pensky-Martens Closed Cup Tester

Standard No.
ASTM D93-06
Release Date
2006
Published By
American Society for Testing and Materials (ASTM)
Status
Replace By
ASTM D93-07
Latest
ASTM D93-20
Scope

1.1 These test methods cover the determination of the flash point of petroleum products in the temperature range from 40 to 360176;C by a manual Pensky-Martens closed-cup apparatus or an automated Pensky-Martens closed-cup apparatus. Note 1 - Flash point determination as above 250176;C can be performed, however, the precisions have not been determined above this temperature. For residual fuels, precisions have not been determined for flash points above 100176;C.

<>

1.2 Procedure A is applicable to distillate fuels (diesel, kerosine, heating oil, turbine fuels), new lubricating oils, and other homogeneous petroleum liquids not included in the scope of Procedure B.

1.3 Procedure B is applicable to residual fuel oils, cutback residua, used lubricating oils, mixtures of petroleum liquids with solids, petroleum liquids that tend to form a surface film under test conditions, or are petroleum liquids of such kinematic viscosity that they are not uniformly heated under the stirring and heating conditions of Procedure A.

1.4 These test methods is applicable for the detection of contamination of relatively nonvolatile or nonflammable materials with volatile or flammable materials.

1.5 The values stated in SI units shall be regarded as the standard. The values given in parentheses are provided for information only.

Note 2

It has been common practice in flash point standards for many decades to alternately use a C-scale or an F-scale thermometer for temperature measurement. Although the scales are close in increments, they are not equivalent. Because the F-scale thermometer used in this procedure is graduated in 5 increments, it is not possible to read it to the 2176;C equivalent increment of 3.6176;F. Therefore, for the purposes of application of the procedure of the test method for the separate temperature scale thermometers, different increments must be used. In this test method, the following protocol has been adopted: When a temperature is intended to be a converted equivalent, it will appear in parentheses following the SI unit, for example 370176;C (698176;F). When a temperature is intended to be a rationalized unit for the alternate scale, it will appear after "or," for example, 2176;C or 5176;F.

This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use. For specific hazards statements, see 6.4, 7.1, 9.3, 9.4, 11.1.2, 11.1.4, and 12.1.2..

ASTM D93-06 history

  • 2020 ASTM D93-20 Standard Test Methods for Flash-Point by Pensky-Martens Closed Cup Tester
  • 2019 ASTM D93-19 Standard Test Methods for Flash Point by Pensky-Martens Closed Cup Tester
  • 2018 ASTM D93-18 Standard Test Method for Iron Bacteria in Water and Water-Formed Deposits
  • 2016 ASTM D93-16a Standard Test Methods for Flash Point by Pensky-Martens Closed Cup Tester
  • 2016 ASTM D93-16 Standard Test Methods for Flash Point by Pensky-Martens Closed Cup Tester
  • 2015 ASTM D93-15a Standard Test Methods for Flash Point by Pensky-Martens Closed Cup Tester
  • 2015 ASTM D93-15 Standard Test Methods for Flash Point by Pensky-Martens Closed Cup Tester
  • 2013 ASTM D93-13e1 Standard Test Methods for Flash Point by Pensky-Martens Closed Cup Tester
  • 2013 ASTM D93-13 Standard Test Methods for Flash Point by Pensky-Martens Closed Cup Tester
  • 2012 ASTM D93-12 Standard Test Methods for Flash Point by Pensky-Martens Closed Cup Tester
  • 2011 ASTM D93-11 Standard Test Methods for Flash Point by Pensky-Martens Closed Cup Tester
  • 2010 ASTM D93-10a Standard Test Methods for Flash Point by Pensky-Martens Closed Cup Tester
  • 2010 ASTM D93-10 Standard Test Methods for Flash Point by Pensky-Martens Closed Cup Tester
  • 2009 ASTM D93-09 Standard Test Methods for Flash Point by Pensky-Martens Closed Cup Tester
  • 2008 ASTM D93-08 Standard Test Methods for Flash Point by Pensky-Martens Closed Cup Tester
  • 2007 ASTM D93-07 Standard Test Methods for Flash Point by Pensky-Martens Closed Cup Tester
  • 2006 ASTM D93-06 Standard Test Methods for Flash Point by Pensky-Martens Closed Cup Tester
  • 2002 ASTM D93-02a Standard Test Methods for Flash-Point by Pensky-Martens Closed Cup Tester
  • 2002 ASTM D93-02 Standard Test Methods for Flash-Point by Pensky-Martens Closed Cup Tester
  • 2000 ASTM D93-00 Standard Test Methods for Flash-Point by Pensky-Martens Closed Cup Tester
  • 1997 ASTM D93-97 Standard Test Methods for Flash-Point by Pensky-Martens Closed Cup Tester
  • 1994 ASTM D93-94 Standard Test Method for Flash Point by Pensky-Martens Closed Tester
  • 1990 ASTM D93-90e1 Standard Test Methods for Flash Point by Pensky-Martens Closed Tester
  • 1985 ASTM D93-85 Standard Test Method for Flash Point by Pensky-Martens Closed Tester
  • 1980 ASTM D93-80e1 Standard Test Methods for Flash Point By Pensky-Martens Closed Tester
  • 1971 ASTM D93-71 Standard Method Of Test For Flash Point By Pensky-Martens Closed Tester



Copyright ©2024 All Rights Reserved