GB/T 20636-2006 Connecting device-Electrical copper conductors-Safety requirements for screw-type and screwless-type clamping units Particular requirements for conductors above 35mm up to 300mm (English Version)
General Administration of Quality Supervision, Inspection and Quarantine of the People‘s Republic of China
Latest
GB/T 20636-2006
Scope
This standard applies to threaded and non-threaded clamps as stand-alone units or as integral parts of equipment. Clamps are used to connect stranded hard and/or soft electrical copper conductors with a cross-sectional area of 35mm2 to 300mm2 (or equivalent AWG/kcmil wire gauge size) (in accordance with GB/T 3956), its rated AC voltage is not greater than 1000V, its frequency is not greater than 1000Hz and its rated DC voltage is not greater than 1500V. This standard applies to clamps intended primarily for the connection of untreated conductors.
GB/T 20636-2006 Referenced Document
GB 17464-1998 Connecting devices--Safety requirements for screw-type and screwless-type clamping units for electrical copper conductors
IEC 60999-1:1999 Connecting devices - Electrical copper conductors - Safety requirements for screw-type and screwless-type clamping units - Part 1: General requirements and particular requirements for clamping units for conductors from 0,2 mm<(hoch)2> up to 35 mm<(hoch)2>
GB/T 20636-2006 history
2006GB/T 20636-2006 Connecting device-Electrical copper conductors-Safety requirements for screw-type and screwless-type clamping units Particular requirements for conductors above 35mm up to 300mm