ASTM D7522/D7522M-15
Standard Test Method for Pull-Off Strength for FRP Laminate Systems Bonded to Concrete Substrate

Standard No.
ASTM D7522/D7522M-15
Release Date
2015
Published By
American Society for Testing and Materials (ASTM)
Status
Replace By
ASTM D7522/D7522M-21
Latest
ASTM D7522/D7522M-21
Scope

5.1 The pull-off strength of a bonded FRP system is an important performance property that has been used in specifications, particularly those for assessing the quality of an application. This test method serves as a means for uniformly preparing and testing bonded FRP systems, and evaluating and reporting the results.

5.2 Variations in results obtained using different devices are possible. Therefore, it is recommended that the type of adhesion test device (including manufacturer and model) be mutually agreed upon between the interested parties.

5.3 This test method is intended for use in both the field and the laboratory.

5.4 The basic material properties obtained from this test method can be used in the control of the quality of adhesives and in the theoretical equations for designing FRP systems for external reinforcement to strengthen existing structures.

1.1 This test method describes the apparatus and procedure for evaluating the pull-off strength of wet lay-up or pultruded (shop-fabricated) Fiber Reinforced Polymer (FRP) laminate systems adhesively bonded to a flat concrete substrate. The test determines the greatest perpendicular force (in tension) that an FRP system can bear before a plug of material is detached. Failure will occur along the weakest plane within the system comprised of the test fixture, FRP laminate, adhesive and substrate.

1.2 This test method is primarily used for quality control and assessment of field repairs of structures using adhesive-applied composite materials.

1.3 This test method is appropriate for use with FRP systems having any fiber orientation or combination of ply orientations comprising the FRP laminate.

1.4 This test method is not appropriate for use as an “acceptance” or “proof” wherein the FRP system remaining intact at a prescribed force is an acceptable result.

1.5 Pull-off strength measurements depend upon both material and instrumental parameters. Different adhesion test devices and procedures will give different results and cannot be directly compared.

1.6 This test method can be destructive. Spot repairs may be necessary. The test method will result in an exposed cut FRP section; repair methods must consider the potential for moisture uptake through this cut section.

1.7 Prior to the installation of some adhesively bonded FRP systems, the substrate concrete must be patched (often to replace lost concrete volume). This test method is not appropriate for determining the pull-off strength of the FRP from the patch material. An additional test method is required to determine the pull-off strength of the patch from the substrate concrete. Throughout this standard, “substrate” is understood to mean the concrete or concrete patch material to which the FRP is adhered.