HG/T 5005-2016
Industrial circulating cooling water and boiler water.Determination of calcium magnesium, iron, zinc and copper.Inductively Coupled Plasma method (English Version)

Standard No.
HG/T 5005-2016
Language
Chinese, Available in English version
Release Date
2016
Published By
Professional Standard - Chemical Industry
Latest
HG/T 5005-2016
Scope
This standard specifies the method for determination of calcium, magnesium, iron, zinc and copper content in boiler water and cooling water by inductively coupled plasma optical emission spectrometry. This standard is applicable to the determination of calcium, magnesium, iron, zinc and copper content in boiler water and cooling water. It is also applicable to the determination of calcium, magnesium, iron, zinc and copper content in various industrial water, raw water and domestic water. This method is suitable for calcium content of 0.02 mg/L~200 mg/L, magnesium content of 0.02 mg/L~200 mg/L, iron content of 0.02 mg/L~100 mg/L, and zinc content of 0.02 mg/L. ~100 mg/L, determination of copper content in the range of 0.02 mg/L~100 mg/L.

HG/T 5005-2016 Referenced Document

  • GB/T 602 Chemical reagent--Preparations of standard solutions for impurity
  • GB/T 6682 Water for analytical laboratory use.Specification and test methods

HG/T 5005-2016 history

  • 2016 HG/T 5005-2016 Industrial circulating cooling water and boiler water.Determination of calcium magnesium, iron, zinc and copper.Inductively Coupled Plasma method