IEC 61869-6:2016
Instrument transformers - Part 6: Additional general requirements for low-power instrument transformers

Standard No.
IEC 61869-6:2016
Release Date
2016
Published By
International Electrotechnical Commission (IEC)
Latest
IEC 61869-6:2016
Replace
IEC 38/501/FDIS:2016 IEC 60044-7:1999(部分代替) IEC 60044-8:2002(部分代替)
Scope
This part of IEC 61869 is a product family standard and covers only additional general requirements for low-power instrument transformers (LPIT) used for a.c. applications having rated frequencies from 15 Hz to 100 Hz covering MV, HV and EHV or used for d.c. applications. This product standard is based on IEC 61869-1:2007, in addition to the relevant product specific standard. This part of IEC 61869 does not cover the specification for the digital output format of instrument transformers. This part of IEC 61869 defines the errors in case of analogue or digital output. The other characteristics of the digital interface for instrument transformers are standardised in IEC 61869-9 as an application of the standards, the IEC 61850 series, which details layered substation communication architecture. This part of IEC 61869 considers additional requirements concerning bandwidth. The accuracy requirements on harmonics and requirements for the anti-aliasing filter are given in the normative Annex 6A.4. The general block diagram of single-phase LPITs is given in Figure 601. According to the technology, it is not absolutely necessary that all parts described in Figure 601 are included in the instrument transformer. As an example, for low-power passive transformers (LPITs without active electronic components) the blocks are composed only with passive components and there is no power supply. Figure 601 - General block diagram of a single-phase LPIT

IEC 61869-6:2016 Referenced Document

  • CISPR 11-2015 Industrial, scientific and medical equipment - Radio-frequency disturbance characteristics - Limits and methods of measurement
  • EN 50160:2010 Voltage characteristics of electricity supplied by public electricity networks (Incorporating corrigendum December 2010)
  • IEC 60068-2-6:2007 Environmental testing - Part 2-6: Tests - Test Fc: Vibration (sinusoidal)
  • IEC 60255-27:2013 Measuring relays and protection equipment - Part 27: Product safety requirements
  • IEC 60603-7-1:2011 Connectors for electronic equipment - Part 7-1: Detail specification for 8-way, shielded, free and fixed connectors
  • IEC 60794-2:2002 Optical fibre cables - Part 2: Indoor cables; Sectional specification
  • IEC 60794-3:2014 Optical fibre cables - Part 3: Outdoor cables - Sectional specification
  • IEC 60812:2006 Analysis techniques for system reliability - Procedure for failure mode and effects analysis (FMEA)
  • IEC 61000-4-1:2006 Electromagnetic compatibility (EMC) - Part 4-1: Testing and measurement techniques - Overview of IEC 61000-4 series
  • IEC 61000-4-2:2008 Electromagnetic compatibility (EMC) - Part 4-2: Testing and measuring techniques - Electrostatic discharge immunity test
  • IEC 61000-4-3:2006 Electromagnetic compatibility (EMC) - Part 4-3: Testing and measurement techniques - Radiated, radio-frequency, electromagnetic field immunity test

IEC 61869-6:2016 history

  • 2016 IEC 61869-6:2016 Instrument transformers - Part 6: Additional general requirements for low-power instrument transformers
Instrument transformers - Part 6: Additional general requirements for low-power instrument transformers