5.1 This test method provides a procedure for performing laboratory tests to evaluate deflagration parameters of dusts.
5.2 The data developed by this test method may be used for the purpose of sizing deflagration vents in conjunction with the nomographs and equations published in NFPA 68, ISO 6184/1, or VDI 3673.
5.3 The values obtained by this testing technique are specific to the sample tested and the method used and are not to be considered intrinsic material constants.
5.4 For dusts with low KSt-values, discrepancies have been observed between tests in 20-L and 1-m3 chambers. A strong ignitor may overdrive a 20-L chamber, as discussed in Test Method E1515 and Refs (1-3).7