ASTM D4787-08
Standard Practice for Continuity Verification of Liquid or Sheet Linings Applied to Concrete Substrates

Standard No.
ASTM D4787-08
Release Date
2008
Published By
American Society for Testing and Materials (ASTM)
Status
Replace By
ASTM D4787-13
Latest
ASTM D4787-13(2018)
Scope

The electrical conductivity of concrete is primarily influenced by the presence of moisture. Other factors, which affect the electrical continuity of concrete structures, include the following:

Presence of metal rebars,

Cement content and type,

Aggregate types,

Admixtures,

Porosity within the concrete,

Above or below grade elevation,

Indoor or outdoor location,

Temperature and humidity, and

Age of concrete.

The electrical conductivity of concrete itself may be successfully used for high-voltage continuity testing of linings applied directly with no specific conductive underlayment installed. However, the voltage required to find a discontinuity may vary greatly from point to point on the structure. This variance may reduce the test reliability.

Although the most common conductive underlayments are liquid primers applied by trowel, roller, or spray, and which contain carbon or graphite fillers, others may take the form of the following:

Sheet-applied graphite veils,

Conductive polymers,

Conductive graphite fibers,

Conductive metallic fibers, and

Conductive metallic screening.

Liquid-applied conductive underlayments may be desirable as they can serve to address imperfections in the concrete surface and provide a better base for which to apply the lining.

This practice is intended for use only with new linings applied to concrete substrates. Inspecting a lining previously exposed to an immersion condition could result in damaging the lining or produce an erroneous detection of discontinuities due to permeation or moisture absorption of the lining. Deposits may also be present on the surface causing telegraphing. The use of a high voltage tester on a previously exposed lining is not recommended because of possible spark through which will damage an otherwise sound lining. A low voltage tester can be used but could produce erroneous readings.

The user may consider this practice when performance requirements of the lining in a specified chemical environment require assurance of a lining free of discontinuities.

Factors affecting the dielectric properties and test voltage shall be considered. Some factors are the curing time of liquid-applied linings; the possible presence of electrically conductive fillers or solvents, or both; the possible presence of air inclusions or voids; and the compatibility of conductive underlayments with the specified lining.

A pulsed dc high voltage may cause a lining to breakdown at a lower voltage than would be the case for a continuous dc voltage.

1.1 This practice covers procedures that may be used to allow the detection of discontinuities in nonconductive linings or other non-conductive coatings applied to concrete substrates.

1.2 Discontinuities may include pinholes, internal voids, holidays, cracks, and conductive inclusions.

1.3 This practice describes detection of discontinuities utilizing a high voltage spark tester using either pulsed or continuous dc voltage.

Note 18212;For further information on discontinuity testing refer to NACE Standard RP0188-88 or Practice D 5162.

1.4 This practice describes procedures both with and without the use of a conductive underlayment.

1.5 The values stated in SI units are to be regarded as standard. The values given in parentheses are for information only.

1.6 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsi......

ASTM D4787-08 history

  • 2018 ASTM D4787-13(2018) Standard Practice for Continuity Verification of Liquid or Sheet Linings Applied to Concrete Substrates
  • 2013 ASTM D4787-13 Standard Practice for Continuity Verification of Liquid or Sheet Linings Applied to Concrete Substrates
  • 2008 ASTM D4787-08 Standard Practice for Continuity Verification of Liquid or Sheet Linings Applied to Concrete Substrates
  • 1993 ASTM D4787-93(1999) Standard Practice for Continuity Verification of Liquid or Sheet Linings Applied to Concrete Substrates