ASTM D7094-17a
Standard Test Method for Flash Point by Modified Continuously Closed Cup (MCCCFP) Tester

Standard No.
ASTM D7094-17a
Release Date
2017
Published By
American Society for Testing and Materials (ASTM)
Status
Replace By
ASTM D7094-23
Latest
ASTM D7094-23
Scope
1.1 This test method covers the determination of the flash point of fuels including diesel/biodiesel blends, lube oils, solvents, and other liquids by a continuously closed cup tester utilizing a specimen size of 2 mL, cup size of 7 mL, with a heating rate of 2.5 °C per minute. 1.1.1 Apparatus requiring a specimen size of 1 mL, cup size of 4 mL, and a heating rate of 5.5 °C per minute must be run according to Test Method D6450. 1.2 This flash point test method is a dynamic method and depends on definite rates of temperature increase. It is one of the many flash point test methods available and every flash point test method, including this one, is an empirical method. NOTE 1—Flash point values are not a constant physical chemical property of materials tested. They are a function of the apparatus design, the condition of the apparatus used, and the operational procedure carried out. Flash point can, therefore, only be defined in terms of a standard test method and no general valid correlation can be guaranteed between results obtained by different test methods or where different test apparatus is specified. 1.3 This test method utilizes a closed but unsealed cup with air injected into the test chamber. 1.4 This test method is suitable for testing samples with a flash point from 35 °C to 225 °C. NOTE 2—Flash point determinations below 35 °C and above 225 °C may be performed; however, the precision has not been determined below and above these temperatures. 1.5 If the user’s specification requires a defined flash point method other than this method, neither this method nor any other test method should be substituted for the prescribed test method without obtaining comparative data and an agreement from the specifier. 1.6 The values stated in SI units are to be regarded as standard. No other units of measurement are included in this standard. Temperatures are in degrees Celsius, pressure in kilo-Pascals. 1.7 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use. For specific warning statements, see 7.2, 8.5, and 10.1.2. 1.8 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.

ASTM D7094-17a Referenced Document

  • ASTM D4057 Standard Practice for Manual Sampling of Petroleum and Petroleum Products
  • ASTM D4177 Standard Practice for Automatic Sampling of Petroleum and Petroleum Products
  • ASTM D6450 Standard Test Method for Flash Point by Continuously Closed Cup (CCCFP) Tester
  • ASTM D6708 Standard Practice for Statistical Assessment and Improvement of Expected Agreement Between Two Test Methods that Purport to Measure the Same Property of a Material*2024-03-01 Update
  • ASTM D93 Standard Test Methods for Flash-Point by Pensky-Martens Closed Cup Tester
  • ASTM E300 Standard Practice for Sampling Industrial Chemicals

ASTM D7094-17a history

  • 2023 ASTM D7094-23 Standard Test Method for Flash Point by Modified Continuously Closed Cup (MCCCFP) Tester
  • 2017 ASTM D7094-17a Standard Test Method for Flash Point by Modified Continuously Closed Cup (MCCCFP) Tester
  • 2017 ASTM D7094-17 Standard Test Method for Flash Point by Modified Continuously Closed Cup (MCCCFP) Tester
  • 2016 ASTM D7094-16 Standard Test Method for Flash Point by Modified Continuously Closed Cup (MCCCFP) Tester
  • 2012 ASTM D7094-12e1 Standard Test Method for Flash Point by Modified Continuously Closed Cup 40;MCCCFP41; Tester
  • 2012 ASTM D7094-12 Standard Test Method for Flash Point by Modified Continuously Closed Cup (MCCCFP) Tester
  • 2004 ASTM D7094-04(2009) Standard Test Method for Flash Point by Modified Continuously Closed Cup (MCCCFP) Tester
  • 2004 ASTM D7094-04 Standard Test Method for Flash Point by Modified Continuously Closed Cup (MCCCFP) Tester
Standard Test Method for Flash Point by Modified Continuously Closed Cup (MCCCFP) Tester